[310]-[311] Partition Identifier Codes
Enter a 6 digit Maintenance Code

[350] – Communicator Format Options

This section determines the communication format used for central
station reporting. From the chart listed below program the 2-digit num-
ber for the desired format for the first and second telephone number

[367] – Opening/Closing Call Direction Options

The first toggle option in this section is used to enable/disable opening/
closing reporting for partition 1. To enable opening/closing reporting
turn option [1] ON. Configure the options as required and press [#] to
exit

.

[377] Communication Variables

NOTE: For UL Installations, the Entry Delay plus the Communications
Delay must not exceed 60 seconds.

[380] – First Communicator Option Codes

[381] – Second Communicator Option Codes

The 3rd toggle option in this section is used to enable/disable auto-
matic SIA reporting. The 5th toggle option is used to enable/disable
automatic Contact ID reporting. Configure the options as required and
press [#] to exit.

NOTE:If the automatic SIA or automatic Contact ID reporting formats
are not used, reporting codes must be programmed. To program
reporting codes refer to the PowerSeries PC1616/1832/1864 Refer-
ence Manual which can be downloaded from the DSC web site at

www.dsc.com

[382] – Third Communicator Option Codes

The 4th toggle option in this section is used to enable/disable Call
Waiting Cancel. Configure the options as required and press [#] to exit.
NOTE:A Call Waiting Cancel on a Non Call Waiting line will prevent
successful connection to the central station.

[701] – First International Options Codes

Option 7 in this section Selects Battery Charge Options.
Select ON for 7 Ahr and 14 Ahr batteries (700 mA charge rate)
Select OFF for Standard 4 Ahr batteries (400 mA charge rate)

[310 System Acct. Code

I___II___II___II___II___II___I

[311] Partition 1 Acct. Code

I___II___II___II___I

Def

Enter 2 digits From Chart Below

04
04

I___II___I
I___II___I

NOTE: 3rd Phone Number follows the format of the

1st Phone Number

01 20BPS, 1400 Hz Handshake
02 20BPS, 2300 Hz Handshake
03 DTMF Contact ID
04 SIA FSK
05 Pager
06 Residential Dial

07 10BPS, 1400 Hz Handshake
08 10BPS, 2300 Hz Handshake
09 Private Line
10 Scantronics 4-8-1 Fast Slo
12 Robofon
13 CESA 200

Opt

Default

Description

1

I__I

ON

1st Telephone Number

OFF

Disabled

2

I__I

ON

2nd Telephone Number

OFF

Disabled

5

I__I

ON

Alternate Communicator

Dsc Power Series Pc1616 Pc1832 Pc1864 V4.2 User Manual Download

OFF

Disabled

Def

Enter 3 digits as indicated below

003 I___II___II___I

003 I___II___II___I

003 I___II___II___I

000 I___II___II___I
030 I___II___II___I
010 I___II___II___I

030 I___II___II___I

030 I___II___II___I
007 I___II___II___I

030 I___II___II___I

000 I___II___II___I

Swinger Shutdown
(Alarms and Rest.
Swinger Shutdown
(Tamper and Rest.
Swinger Shutdown
(Maint. and Rest.
Communication Delay
AC Failure Comm Delay
TLM Trouble Delay

Test Transmission Cycle
(land line)
Not Used
Zone low Battery
Transmission Delay
Delinquency Transmis-
sion Cycle
Communications
Cancelled Window

(001-014 Transmissions)

(001-014 Transmissions,
000=disabled)
(001-014 Transmissions,
000=disabled)
(000-255 seconds)
(001-255 minutes)
No. of checks req’d (003-
255)
(001-255 days/minutes)

(000-255 days)

Dsc power series pc1616 pc1832 pc1864 v4.2 user manual download

(000-255 days/hours)

(000-255 minutes)

NOTE: Option 1 is defaulted to 001 for CP-01 Installations

Option 4 is defaulted to 030 for CP-01 Installations
Option 11 is defaulted to 005 for CP-01 Installations

Opt

Default

Description

1

I__I

ON

Communications Enabled

OFF

Communications Disabled

2

I__I

ON

Restorals on Bell Time-out

OFF

Restorals Follow Zones

3

I__I

ON

Pulse Dialing

OFF

DTMF Dialing

5

I__I

ON

3rd Telephone Number Enabled

OFF

3rd Telephone Number Disabled

8

I__I

ON

Delinquency Follows Zone Activity (Hours)

OFF

Delinquency Follows Arming (Days)

Opt

Default

Description

3

I__I

ON

SIA Sends Programmed Reporting Codes

OFF

SIA Sends Automatic Reporting Codes

5

I__I

ON

Contact ID Uses Programmed Reporting
Codes

OFF

Contact ID Uses Automatic Reporting Codes

Opt

Default

Description

4

I__I

ON

Call Waiting Cancel Enabled

OFF

Call Waiting Cancel Disabled

5

I__I

ON

T-Link Interface Enabled

OFF

T-Link Interface Disabled

Opt

Default

Description

7

I__I

ON

High Current Battery Charge (700mA)

OFF

Standard Battery Charge Rate (400mA)

Advertising
This manual is related to the following products:
Popular Brands
Popular manuals
Advertising

Hardware Installation (Cont.)

4. AUX Power Wiring

The control panel can provide a maximum of 700mA of current for modules, powered detectors, relays, LED’s etc.… If the total current
required exceeds 700mA an additional power supply is required (e.g.,PC5200, PC5204). See list below.

NOTE: Min/max operating voltages for devices, sensors and modules is 9.5V

DC

- 14V

DC

Refer to the list of Compatible Devices on the first page for the current draw of individual devices

5. PGM Wiring

PGMs switch to ground when activated by control panel.
Connect the positive side of the device to be activated to the AUX+
Terminal. Connect the negative terminal to the PGM.
current output is as follows

PGM 1, 3, 4 .................... 50mA

PGM 2 .......................... 300mA

For currents levels greater than 300mA a relay is required.
PGM2 can also be used for 2-wire smoke detectors.

NOTE: Use SEOL resistors on Fire Zones ONLY.

PGM 1, LED Output with current limiting resistor and Optional Relay

driver output

2-wire Smoke Detectors Initiating Circuit

Style B (Class B), Supervised, Power Limited

Compatibility Identifier ........................................................ PC18-1

Dsc Power Series Pc1616 Pc1832 Pc1864 V4.2 User Manual

DC Output Voltage..................................................... 9.8-13.8 VDC

Detector Load ............................................................. 2 mA (MAX)

Single-end-of-line (SEOL) Resistor ..................................... 2200

Loop Resistance............................................................24

Ω (MAX)

Standby Impedance.................................................. 1020

Ω (ΝΟΜ)

Alarm Impedance ........................................................570

Ω (MAX)

Alarm Current ............................................................ 89 mA (MAX)

Compatibility ID For FSA-210B Series is: FS200

4-wire Smoke Detectors

6. Telephone Line Wiring

Wire the telephone connection terminals (TIP, Ring, T-1, R-1) to an
RJ-31x Connector as indicated.

For connection of multiple devices to the telephone line, wire in the
sequence indicated.
Telephone format is programmed in section [350].
Telephone Call Directions are programmed in section [351]-[376].

7. Ground

8. Battery

9. AC Wiring

Ground Installation

A sealed, rechargeable, lead
acid battery or gel type battery is
required to meet UL require-
ments for power standby times.
NOTE: UL Residential/Commer-
cial Burglary installations require
4Hrs Power Standby time.
NOTE: UL/ULCResidential Fire
& Home Care installations
require 24 Hr power standby.
ULC Commercial Burglary
and Fire monitoring installations
require 24 Hr power standby.

Standby Battery Guide

Battery Charging Current: 400 mA

Batt

Standby

Size

4Hr

24Hr

-------------------------------------------------
4Ahr

700mA

----

7Ahr

700mA

180mA

14Ahr

700mA

470mA

NOTE:

Replace batteries every 3-5 years.
Battery capacity will deteriorate with
age and number of charge/discharge
cycles

AC Wiring

UL Listed Installations
Primary:
120VAC/60Hz./0.33A
Secondary: 16.5VAC/40VA
DSCPTD 1640 Plug-in, Class 2
Transformer.

NOTE: Do not connect trans-
former to a receptacle controlled
by a switch.
(UL Listed Installations
Only)

RM-1/RM-2 POWER LOOP

SUPERVISORY RELAY

T-1

R-1
TIP

RING

RJ-31X

Tighten nut to break paint and make

good connection to the cabinet